Differential signaling does not make receiver input voltage limits disappear. In an RS-485 link, ground offset between nodes can shift both bus wires relative to a receiver’s local reference. Review that common-mode condition separately from the differential voltage carrying the data.
Define every reference point
TI’s RS-485 design guide discusses ground-potential differences and grounding or isolation choices for remote links. Its discussion shows why a communication test performed between nearby, commonly powered boards does not represent every installed condition.
Draw each node’s supply reference, chassis connection, cable reference conductor and shield connection. Identify which connections are intentional and which arise through programming equipment or other interfaces. Keep protective grounding requirements separate from signal-reference decisions and have the complete installation assessed by the appropriate responsible engineer.
Evaluate the receiver’s actual voltages
For every transmitting node, determine the two bus-wire voltages relative to each receiving node’s local circuit reference. Calculate their average as common mode and their difference as the signal. Compare both with the selected transceiver’s operating limits, using the applicable supply and temperature conditions.
Include credible DC ground offset and expected disturbances. Do not substitute an absolute maximum rating for a guaranteed operating range. A part surviving an imposed voltage does not establish that it will receive data accurately under that condition.
Review current paths as well as voltage
Identify where current can flow when the node references differ. Examine the complete reference and shield arrangement, including equipment connected during service. A connection added to improve communication can also change circulating-current paths, so its purpose and implementation need to be explicit.
If isolation is used, review both signal and power paths and the intended reference of the bus-side circuitry. Avoid assuming that an isolated data channel alone defines the behavior of every other connection between the two systems.
Test a documented envelope
Use an appropriate controlled test arrangement to evaluate the specified reference-offset range while observing receiver inputs and communication errors. Keep the test within the component and equipment ratings. Include the longest intended cable and the permitted node power states where they affect the result.
Record the transceiver, wiring arrangement, applied offset and measured bus voltages together. State the verified envelope and the installation assumptions on which it depends. This makes future cable, grounding or power-source changes reviewable and prevents a working differential waveform from being mistaken for proof that every receiver remains within its allowed common-mode range. Include temporary service-equipment connections in the documented reference diagram.